Your location:Home > PRODUCTS > kanomax TABMASTER MINI AIRFLOW CAPTURE HOOD – MODEL 6750

Product Name:kanomax TABMASTER MINI AIRFLOW CAPTURE HOOD – MODEL 6750

kanomax TABMASTER MINI AIRFLOW CAPTURE HOOD – MODEL 6750
  • kanomax TABMASTER MINI AIRFLOW CAPTURE HOOD – MODEL 6750
  • kanomax TABMASTER MINI AIRFLOW CAPTURE HOOD – MODEL 6750
  • kanomax TABMASTER MINI AIRFLOW CAPTURE HOOD – MODEL 6750
  • Description
  • Details
  • Optional Accessories
  • The Kanomax TABmaster Mini Airflow Capture Hood is the perfect HVAC testing tool for residential or small space applications. This direct reading device gives you highly accurate and repeatable measurements in the field. With a compact and lightweight design, operators can quickly check supply and return airflow measurements in buildings.


    With its transparent hood design users can easily line up with the register they measure. Capable of recording up to 6000 data points, the TABmaster Mini also comes equipped with Bluetooth? wireless capability to wirelessly start/stop measurements, as well as communicate with the Kanomax TABViewer App.


    Features & Benefits

    Airflow ranges: 8 to 600 m3/h

    Simultaneously measures and displays air flow and temperature

    Store up to 6000 measurements

    Lightweight and one-hand operation design

    Bluetooth? wireless capability

    Transparent flow hood for easy register alignment

    Wireless control and communication via Kanomax Smart App

    Accurately measure small registers/vents in residential buildings

    Has applications for both residential and commercial buildings


    Main Unit Specifications

    AirflowRange8 to 600 m3/h (5 to 353 CFM)
    Accuracy

    +/- 3% + 1 digit m3/h (@ 8 to 350 m3/h ranges)

    +/- 5% + 1 digit m3/h (@ 350 to 600 m3/h ranges)

    Resolution1 m3/h
    TemperatureRange32 to 122°F (0 to 50°C)
    Accuracy+/- 0.5°C
    Resolution0.1°C
    General Specifications

    Operating Temperature0 to 50°C (with no condensation)
    Storage Temperature-10 to 50°C (with no condensation)
    Standard Hood Dimensions13.97 x 13.97 inches (355 mm x 355) mm
    DataloggingUp to 6,000 Measurements
    Power Supply4 x AA batteries or optional AC Adapter
    Weight & DimensionsMain body: 3.3 lbs (1.5 kg), Micromanometer: 2.4 x 4.7 x 1.2 inches (60 x 120 x 34 mm)
    Warranty1 year
    What’s included

    Instrument (meter, standard hood, rod, meter fixture, meter cable)

    Carrying case

    USB cable

    4 x AA batteries

    Software (provided with CD-ROM)

    User manual

    Calibration certificate with a test sheet


  • Your Name:
  • Telephone:
  • E-mail:

Attachment list: